Optional Modules and Accessories
Product Description
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 (red) is available as an option. The dress panel restricts access to the sys-
tem wiring while allowing access to the membrane switch panel. The Canadian version is supplied
standard with a modified dress panel.
TR-CE Trim-ring
A trim-ring TR-CE (red) is available as an option. The trim-ring allows semi-flush mounting of the
cabinet.
Battery Box
The BB-55F or BB-26 battery box may be used to house two batteries greater than 18 Amp Hour.
The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
Battery Chargers
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP
battery charger must be disabled, through software programming, when using the CHG-75. The
charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the
charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from
the control panel. Refer to the CHG-75 Manual for additional information.
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP
battery charger must be disabled, through software programming, when using the CHG-120F. The
batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet
away from the control panel. Note that when using the BB-55F for housing the charger and
batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for
additional information.