B.6 template 6: single hazard - cross-zone nac, B.6: template 6: single hazard - cross-zone nac – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 134
134
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
FACP Configuration Templates
Template 6: Single Hazard - Cross-Zone NAC
B.6 Template 6: Single Hazard - Cross-Zone NAC
Table Legend:
* = shows relationship only, will not activate a release circuit
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66).
Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).
Input Zone Types:
•
Zone 1 = circuit with type code of 2-wire smoke
•
Zone 2 = circuit with type code of 2-wire smoke
•
Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release
•
Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to “Abort Type” on page 71)
•
Zone 5 = circuit with type code of Discharge Pressure Switch
•
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
•
Output 1 = Release Circuit 1 - Supervised for shorts
•
Output 2 = Alarm NAC - silenceable, programmed for Cross-Zone coded operation for
Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on
page 66)
•
Output 3 = Release Stage Pre-Discharge - silenceable, programmed Release Stage Pre-
Discharge operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or
Release Circuit 2:” on page 66)
Template 6: Single Hazard - Cross-Zone NAC
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE
SMOKE
2-WIRE
SMOKE
MANUAL
RELEASE
ABORT
DISCHARGE
PRESSURE
SUPERVISORY
#1 RELEASE CIRCUIT 1
C1
C1
X
X*
X*
#2 ALARM NAC
Xc
Xc
#3 RELEASE STATE
PRE-DISCHARGE
Xr
Xr
Xr
Xr
#4 RELEASE STAGE
DISCHARGE
Xr
Xr
Xr
Xr