B.2 template 2: single zone system with horn, B.2: template 2: single zone system with horn – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 122
122
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
FACP Configuration Templates
Template 2: Single Zone System With Horn
B.2 Template 2: Single Zone System With Horn
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).
Input Zone Types:
•
Zone 1 = circuit with type code of 2-wire smoke
•
Zone 2 = circuit with type code of 2-wire smoke
•
Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release
•
Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to “Abort Type” on page 71)
•
Zone 5 = circuit with type code of Pull Station
•
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
•
Output 1 = Release Circuit 1 - Unsupervised for shorts
•
Output 2 = Release Stage NAC - silenceable, programmed Release Stage operation (refer to
“Release Stage/NAC Operation” on page 98)
•
Output 3 = Alarm NAC - silenceable, coded for steady on
•
Output 4 = Alarm NAC - silenceable, coded for steady on
Timers
•
Pre-Discharge Delay - set for 30 seconds
•
Discharge - set for 1 minute
•
Waterflow Delay Timer - set for 90 seconds
•
AC Loss Delay Timer - set for 2 hours
Template 2: Single Zone System with Horn
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE
SMOKE
2-WIRE
SMOKE
MANUAL
RELEASE
ABORT
PULL
STATION
SUPERVISORY
#1 RELEASE CIRCUIT 1
X
X
X
X
#2 RELEASE STAGE NAC
Xr
Xr
Xr
#3 ALARM NAC
X
#4 ALARM NAC
X
X
X