Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 72
72
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
Programming
Master Programming Level
Pre-Discharge
There are two Pre-discharge timers which allows each releasing circuit to be programmed with
different pre-discharge delay times. The factory default setting for each Pre-discharge timer is 0 for
no delay. To select a Pre-discharge delay of 01 to 60 seconds, press 1 for Pre-Discharge1 or 2 for
Pre-Discharge2 while viewing Timer Screen #1. The following display will appear:
This screen allows the user to program a specific delay time before the releasing circuit begins an
agent release during an alarm condition. A flashing cursor is positioned in the lower left corner of
the display. Enter a Pre-Discharge delay time consisting of two digits, such as 05 for five seconds.
Upon entering the second digit, the time delay will be stored in the control panel memory and the
display will return to the Delay Screen which will indicate the new Pre-Discharge delay time. In
this example, when the corresponding agent releasing circuit is activated, it will delay agent release
for five seconds.
Note that if a Manual Release is activated, the Discharge Delay time will be ignored and the
release will begin immediately.
Discharge Timer
There are two Discharge timers which allows each releasing circuit to be programmed with
different discharge delay times. The Discharge Timers determine how long an agent release will
continue once activated. The factory default setting for the Discharge Timers is Always On. To
program the Discharge Timer, press 3 for Discharge 1 while viewing the Timer Screen #1 or press 1
for Discharge 2 while viewing Timer Screen #2. The following display will appear:
Pressing 1 while viewing the Discharge Setup screen will program the releasing circuit to continue
an agent release until the panel is reset.
PRE-DISCHARGE DELAY
RANGE 00-60 SECONDS
Pre-Discharge Setup Screen
DISCHARGE
1=ALWAYS ON
2=ENTER MINUTES
Discharge Setup Screen