B.11 template 11: agent/waterflow - cross-zone, B.11: template 11: agent/waterflow - cross-zone – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 149
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
149
Template 11: Agent/Waterflow - Cross-Zone
FACP Configuration Templates
B.11 Template 11: Agent/Waterflow - Cross-Zone
Table Legend:
* = shows relationship only, will not activate a release circuit
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to Cross Zone in “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66).
Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).
Input Zone Types:
•
Zone 1 = circuit with type code of 2-wire smoke
•
Zone 2 = circuit with type code of 2-wire smoke
•
Zone 3 = circuit with type code Manual Release/Abort Switch Combo - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to “Abort Type” on page 71)
•
Zone 4 = circuit with type code of Discharge Pressure Switch
•
Zone 5 = circuit with type code of Waterflow
•
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
•
Output 1 = Release Circuit 1 - Supervised for shorts
•
Output 2 = Release Circuit 2 - Supervised for shorts
•
Output 3 = Alarm NAC - silenceable, programmed for Cross-Zone Pre-Discharge coded
operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit
2:” on page 66)
•
Output 4 = Release Stage Coded - nonsilenceable, programmed Release Stage Coded operation
for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on
page 66)
Template 11: Agent/Waterflow - Cross-Zone
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE
SMOKE
2-WIRE
SMOKE
MANUAL
RELEASE/ABORT
SW. COMBO
DISCHARGE
PRESSURE
WATERFLOW
SUPERVISORY
#1 RELEASE CIRCUIT 1
C1
C1
X
X*
#2 RELEASE CIRCUIT 2
C2
C2
X
X*
#3 ALARM NAC
Xc
Xc
X
X
#4 RELEASE STAGE
CODED
Xr
Xr
Xr
Xr