B.3 template 3: single hazard - cross-zone, B.3: template 3: single hazard - cross-zone – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 125
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
125
Template 3: Single Hazard - Cross-Zone
FACP Configuration Templates
B.3 Template 3: Single Hazard - Cross-Zone
Table Legend:
* = shows relationship only, will not activate a release circuit
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to Cross Zone in “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66).
Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).
Input Zone Types:
•
Zone 1 = circuit with type code of 2-wire smoke
•
Zone 2 = circuit with type code of 2-wire smoke
•
Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release
•
Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to “Abort Type” on page 71)
•
Zone 5 = circuit with type code of Discharge Pressure Switch
•
Zone 6 = circuit with type code of Supervisory
Output Circuit Types
•
Output 1 = Release Circuit 1 - Supervised for shorts
•
Output 2 = Alarm NAC - silenceable, programmed for cross-zone coded operation for Release
Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66.)
•
Output 3 = Release Stage Pre-Discharge - silenceable, programmed Release State Pre-
Discharge operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or
Release Circuit 2:” on page 66.)
•
Output 4 = Release Stage Discharge - nonsilenceable, programmed Release Stage Discharge
operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit
2:” on page 66.)
Template 3: Single Hazard - Cross-Zone
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE
SMOKE
2-WIRE
SMOKE
MANUAL
RELEASE
ABORT
DISCHARGE
PRESSURE
SUPERVISORY
#1 RELEASE CIRCUIT 1
C1
C1
X
X*
X*
#2 ALARM NAC
Xc
Xc
#3 RELEASE STAGE
PRE-DISCHARGE
Xr
Xr
Xr
Xr
#4 RELEASE STAGE
DISCHARGE
Xr
Xr
Xr
Xr