3 controls and indicators, Controls and indicators – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 17
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
17
Controls and Indicators
Product Description
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and indi-
cators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys,
including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•
Acknowledge/Step
•
Alarm Silence
•
Drill
•
System Reset (lamp test)
Service/program keys:
•
Keys labeled 1 to 9
•
* key
•
# key
•
0 (recall) key
•
1st Event key
•
Clear key
•
Escape key
•
Mode key
•
Four cursor keys (up, down, left and right)
•
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi-
tions.
Indicators
Indicators are provided to annunciate the following conditions:
•
Fire Alarm - red indicator
•
Supervisory - yellow indicator
•
AC Power - green indicator
•
System Trouble - yellow indicator
•
Alarm Silenced - yellow indicator
•
Discharge - red indicator
•
Pre-discharge - red indicator
•
Abort - yellow indicator
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervi-
sory conditions as follows:
•
Alarm - on steady
SYSTEM ALL NORMAL
10:00A 012106
Figure 1.2 Membrane/Display Panel
RP20
01
kypd