5 ann-i/o led driver module, Ann-i/o board layout, Specifications – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 44: Ann-i/o led driver module, Ann-i/o board layout specifications
44
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
Installation
ANN-BUS Devices
2.7.5 ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The following sections describe hardware installation. Refer to the section
titledSection 3.5.7, “ANN-BUS”, on page 78 for programming information.
ANN-I/O Board Layout
Figure 2.22 illustrates the ANN-I/O board showing locations of screw terminals for connection to
the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID
number.
Specifications
•
Max. ANN-BUS Voltage: 28 VDC
•
Max. Current:
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
•
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
For indoor use in a dry location only
Figure 2.22 ANN-I/O Board Layout
ANN-BUS (ID#)
Address DIP
switch
ANN-BUS Connector
Terminals not used (future)