Ann-led board layout and connection to facp, 7 ann-rly relay module, Specifications – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 47: Ann-rly relay module
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
47
ANN-BUS Devices
Installation
ANN-LED Board Layout and Connection to FACP
Figure 2.25 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
2.7.7 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compat-
ible FACP.
Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Relay Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
•
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
For indoor use in a dry location only
Figure 2.25 ANN-LED Board Layout and Connection to FACP
FACP
ANN-LED
Primary ANN-BUS
+24 VDC
-24 VDC
ANN-BUS (ID#)
Address DIP switch