62
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
Programming
Master Programming Level
Pressing the down arrow key while viewing the Edit Output Type Screen will display additional
screens with the following types:
• Release Circuit 1
• Release Circuit 2
• Alarm NAC
• Waterflow NAC
• Release Stage Coded NAC (Refer to “Release Stage/NAC Operation” on page 98.)
• Release Stage Discharge NAC (Refer to “Release Stage/NAC Operation” on page 98.)
• Release Stage Pre-Discharge NAC (Refer to “Release Stage/NAC Operation” on page 98.)
• Horn NAC
• Strobe NAC
• Supv Bell NAC
• Trouble Bell NAC
Press the number key corresponding to the desired Output Type to program the selected Output.
Release Circuit 1 or Release Circuit 2
If Release Circuit 1 or Release Circuit 2 is selected as the Output Type, the following subscreen
will be displayed:
This screen allows the programmer to select whether or not to supervise the Releasing Circuit
Output for shorts.
•
UNSUPV SHORTS - this option should normally be selected when a releasing solenoid is
connected to the output so the solenoid coil is not supervised for shorts
•
SUPV SHORTS - this option, which supervises for shorts, should only be selected when the
REL-4.7K option is installed in series with the solenoid coil.
Release Stage NAC
If Release Stage Coded, Release Stage Discharge or Release Stage Pre-Discharge is selected as the
Output Type, the following subscreen will be displayed:
EDIT RELEASE CIR #
1=UNSUPV SHORTS
2=SUPV SHORTS
NOTE: Release circuits may be directly activated by a single input zone or may be activated
using cross-zoned inputs. Refer to “Circuit Mapping and Cross-Zoning” on page 112 for a
description of cross-zoning and input to output circuit mapping.
RELEASE STAGES
1=RELEASE 1 ONLY
2=RELEASE 2 ONLY