78
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
Programming
Master Programming Level
Secondary ANN-BUS Option
Pressing 2 while viewing System Setup Screen #3 allows the user to enable the secondary
ANN-BUS. The secondary ANN-BUS must be enabled if any modules are connected to the
ANN-SEC option card at J13. To enable the Secondary ANN-BUS, press 1 while viewing the
SEC-ANN screen so that the display reads SEC ANN Enabled Yes. Each press of the 1 key will
cause the display to toggle between SEC ANN Enabled Yes and SEC ANN Enabled No. The factory
default setting is ANN-SECONDARY Enabled No.
3.5.7 ANN-BUS
Optional ANN-BUS devices available for the FACP include annunciators, relay modules and
printer connection for acquiring hardcopy printouts of panel data. Pressing 1 while viewing
Programming Screen #3 will cause the control panel to display the following screens.
An ANN-S/PG Printer module, ANN-80 LCD annunciator module and ANN-RLY relay module
can be programmed into the FACP. These devices communicate with the FACP over the ANN-
BUS terminals on the control panel.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads ANN-
BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-BUS
Enabled Yes and ANN-BUS Enabled No.
ANN-BUS Modules
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-
BUS addresses for the module(s). The following screen will be displayed.
SYSTEM SETUP
1=CANADIAN OPTION
2=SEC ANN ENABLE
System Setup Screen #3
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
Programming Screen #3
ANN-BUS
1=BUS ENABLED NO
2=BUS MODULES
3=AUTO CONFIGURE
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS MODULES
1=ADDR. 1 NONE
2=ADDR. 2 NONE
3=ADDR. 3 NONE
ANN-BUS Module Screen #1