Section 3: Programming
3.1 User Programming
The FACP is completely field programmable using the panel keypad and requires no special soft-
ware skills. While programming the FACP, the fire protection capabilities of the control panel are
enabled. Programming Mode times-out after 10 minutes of inactivity.
Program Templates have been provided to allow the panel to be quickly programmed with typical
job-site configurations. Refer to “Circuit Mapping and Cross-Zoning” on page 112 for an
explanation of mapping and cross-zoning and “FACP Configuration Templates” on page 118 for a
detailed description of each template.
Site-specific programming may be accomplished:
• by Manual programming or editing, using the FACP keypad
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or
supervisory event exists at the panel, the event must be cleared before entering Programming mode.
The exception to this is the programmer/operator can access Programming mode if the supervisory
is due to the Disable Release event. Refer to Table 3.1 on page 56.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program feature or option
Permitted in UL 864? (Y/N)
Possible settings
Settings permitted in UL
864
ANN-80 Lock Enable
Y
Lock Enable Yes
Lock Enable No
Refer to Lock Enable in
Lock Enable Yes
Combo
Y
One Waterflow and one
Supervisory device
Combo w/AutoResettable
Superv
Y
Refer to Table 3.1 on
One Waterflow and one
Supervisory device
SYSTEM ALL NORMAL