B.10 template 10: dual hazard - single detector, B.10: template 10: dual hazard - single detector – Fire-Lite MRP-2002C Agent Release Control Panel User Manual
Page 146
146
MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013
FACP Configuration Templates
Template 10: Dual Hazard - Single Detector
B.10 Template 10: Dual Hazard - Single Detector
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).
Input Zone Types:
•
Zone 1 = circuit with type code of 2-wire smoke
•
Zone 2 = circuit with type code of 2-wire smoke
•
Zone 3 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to “Abort Type” on page 71)
•
Zone 4 = circuit with type code of 2-wire smoke
•
Zone 5 = circuit with type code of 2-wire smoke
•
Zone 6 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to “Abort Type” on page 71)
Output Circuit Types:
•
Output 1 = Release Circuit 1 - Supervised for shorts
•
Output 2 = Release Circuit 2 - Supervised for shorts
•
Output 3 = Release Stage Coded - silenceable, programmed Release Stage Coded operation for
Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on
page 66)
•
Output 4 = Release Stage Coded - silenceable, programmed Release Stage Coded operation for
Release Circuit 2 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on
page 66)
Timers
•
Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 30 seconds
•
Discharge: Release 1 - set for Always On; Release 2 - set for Always On
•
Waterflow Delay Timer - set for 90 seconds
•
AC Loss Delay Timer - set for 2 hours
Template 10: Dual Hazard - Single Detector
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE
SMOKE
2-WIRE
SMOKE
MANUAL
RELEASE/ABORT
SW. COMBO
2-WIRE
SMOKE
2-WIRE
SMOKE
MANUAL
RELEASE/ABORT
SW. COMBO
#1 RELEASE CIRCUIT 1
X
X
X
#2 RELEASE CIRCUIT 2
X
X
X
#3 RELEASE STAGE
CODED
Xr
Xr
Xr
#4 RELEASE STAGE
CODED
Xr
Xr
Xr