6 system settings, 7 timers, System settings 4.15.7: timers – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 98

98
MRP-2001 Series Manual — P/N 53040:D 12/15/2010
Operating Instructions
Read Status
4.15.6 System Settings
Pressing 3 while viewing Read Status Screen #2 will display the following screens:
The operator can view the system settings options that have been programmed into the FACP.
4.15.7 Timers
Pressing 1 while Read Status Screen #3 will display the following screens:
These screens allow the operator to view the various timer settings.
SYSTEM SETTINGS
FACTORY BANNER
SYSTEM SETTINGS
FUTURE USE
TROUBLE REMIND NO
CHARGER DISABLE NO
SYSTEM SETTINGS
CANADIAN OPTION NO
SEC ANN ENABLE NO
READ STATUS
1=TIMERS
2=DAYLIGHT SAVINGS
3=HISTORY
Read Status Screen #3
TIMERS
SOAK 1 10 MIN
SOAK 2 10 MIN
WATERFLOW DELAY 0 S
TIMERS
AC LOSS DELAY 2 HR