Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 119
MRP-2001 Series Manual — P/N 53040:D 12/15/2010
119
Template 5: Single Hazard - 3 Zones and Low Pressure
FACP Configuration Templates
B.5 Template 5: Single Hazard - 3 Zones and Low Pressure
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
•
Zone 1 = 2-wire smoke
•
Zone 2 = Fire
•
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•
Zone 4 = Manual Release
•
Zone 5 = Pull Station
•
Zone 6 = Low Pressure
Output Circuit Types:
•
Output 1 = Alarm NAC, silenceable, coded for steady on
•
Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.),
silenceable, coded for steady on
•
Output 3 = Supervisory Bell NAC, silenceable, coded for steady on
•
Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
•
Soak Timer 1 - set for 10 minutes
•
Soak Timer 2 - set for 10 minutes
•
Waterflow Delay Timer - set for 10 seconds
•
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1
•
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is a
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds
•
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
Template 5: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL
RELEASE
PULL
STATION
LOW
PRESS.
#1 ALARM NAC
X
X
X
X
#2 WATERFLOW NAC
X
#3 SUPV. BELL NAC
X
#4 RELEASE SOLENOID 1
X
X
X
X