Enabled, Type, Enabled type – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 58
58
MRP-2001 Series Manual — P/N 53040:D 12/15/2010
Programming
Master Programming Level
The Output Circuits can be configured independently by pressing 1 for Output 1, 2 for Output 2, 3
for Output 3 or 4 for Output 4.
To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:
Enabled
Pressing 1 while viewing Output Screen #1 will cause the display to change to Enabled No. This
will prevent the selected main circuit board NAC from activating its devices. Each press of the 1
key will cause the display to toggle between Enabled Yes and Enabled No.
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is enabled.
The exception is when a Release Circuit is disabled, a supervisory will be logged on the FACP until
the circuit is enabled.
Type
Pressing 2 while viewing Output Screen #1 will cause the following screen to be displayed:
OUTPUT #
1=ENABLED YES
2=TYPE ALARM NAC
Output Screen #1
Output Screen #2
OUTPUT #
1=SILENCE NON-SIL
2=AUTO SILENCE NO
3=SIL INHIBIT NO
Output Screen #3
OUTPUT #
1=CODING
STEADY
NAC #
1=ENABLED
2=TYPE ALARM NAC
NAC Screen #1
EDIT OUTPUT # TYPE
1=RELEASE CIRCUIT 1
2=RELEASE CIRCUIT 2
3=ALARM NAC
Edit Output # Type Screen