4 output circuits, Output circuits, Outputs/notification appliance/releasing circuits – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual

Page 26

background image

26

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

Installation

Output Circuits

2.4 Output Circuits

2.4.1 Outputs/Notification Appliance/Releasing Circuits

Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and
provides special application power. Refer to the Device Compatibility Document for a listing of
compatible notification appliances.

The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter
module. Refer to “CAC-5X Class A Converter Module” on page 29.

Figure 2.7 NAC/Output Connections

Class B Notification Appliance Circuits (supervised and power-limited)

4.7 K

, ½ watt resistor P/N:71252

Dummy load any unused
circuits (P/N: 71245)

Polarized Bell

Polarized Strobe

Polarized Horn

Polarized Horn

Polarized Bell

Notification Appliance Circuits

polarity shown in alarm condition

rp20

01

na

c.cdr

Releasing Solenoid

Polarized Strobe

+ - + -

+ - + -

Note: Short Circuit Supervision must be enabled when using the
REL-4.7K for Canadian Applications. Refer to the section titled
“Release Circuit 1 or Release Circuit 2” on page 59 for information
on enabling short circuit supervision.

Releasing Circuit for

Canadian Applications

REL-4.7K

Unused Output

Circuit 4.7K

dummy load resistor

PN 71245