MRP-2001 Series Manual — P/N 53040:D 12/15/2010
Installation
Output Circuits
2.4 Output Circuits
2.4.1 Outputs/Notification Appliance/Releasing Circuits
Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and
provides special application power. Refer to the Device Compatibility Document for a listing of
compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter
module. Refer to “CAC-5X Class A Converter Module” on page 29.
Figure 2.7 NAC/Output Connections
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 K
, ½ watt resistor P/N:71252
Dummy load any unused
circuits (P/N: 71245)
Polarized Bell
Polarized Strobe
Polarized Horn
Polarized Horn
Polarized Bell
Notification Appliance Circuits
polarity shown in alarm condition
rp20
01
na
c.cdr
Releasing Solenoid
Polarized Strobe
+ - + -
+ - + -
Note: Short Circuit Supervision must be enabled when using the
REL-4.7K for Canadian Applications. Refer to the section titled
“Release Circuit 1 or Release Circuit 2” on page 59 for information
on enabling short circuit supervision.
Releasing Circuit for
Canadian Applications
REL-4.7K
Unused Output
Circuit 4.7K
dummy load resistor
PN 71245