beautypg.com

Section 3: programming, 1 user programming, User programming – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual

Page 47

background image

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

47

Section 3: Programming

3.1 User Programming

The FACP is completely field programmable using the panel keypad and requires no special
software skills. While programming the FACP, the fire protection capabilities of the control panel
are enabled. Programming Mode times-out after 10 minutes of inactivity.

Program Templates have been provided to allow the panel to be quickly programmed with typical
job-site configurations. Refer to “Circuit Mapping and Cross-Zoning” on page 105 for an
explanation of mapping and cross-zoning and “FACP Configuration Templates” on page 110 for a
detailed description of each template.

Site-specific programming may be accomplished:

by Manual programming or editing, using the FACP keypad

The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:

Read Status mode can be entered while the panel is in any mode of operation. If an alarm or
supervisory event exists at the panel, the event must be cleared before entering Programming mode.
The exception to this is the programmer/operator can access Programming mode if the supervisory
is due to the Disable Release event. Refer to Table 3.1 on page 53.

To access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the

Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be

limited to specific values or not used at all as indicated below.

Program feature or

option

Permitted in UL 864? (Y/N)

Possible settings

Settings permitted in UL

864

ANN-80 Lock Enable

Y

Lock Enable Yes

Lock Enable No

Refer to Lock Enable in “ANN-80

Options” on page 77

Lock Enable Yes

Combo

Y

Refer to Table 3.1 on page 53.

One Waterflow and one

Supervisory device

Combo w/AutoResettable

Superv

Y

Refer to Table 3.1 on page 53.

One Waterflow and one

Supervisory device

SYSTEM ALL NORMAL
10:00A 092105

WATER RELEASE PANEL
1=READ STATUS MODE
2=PROGRAMMING MODE