beautypg.com

Appendix f: wire requirements – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual

Page 136

background image

136

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

Appendix F: Wire Requirements

Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each
circuit. Reference the chart below to specify wire requirements and limitations for each circuit.

CIRCUIT CONNECTIONS

WIRE REQUIREMENTS

Circuit Type

Circuit Function

Wire Type and

Limitations

Recommended

Max. Distance

Feet (meters)

Wire Gauge

Initiating
Device Circuit
(power-limited)

Connects to
Initiating Devices

Untwisted, unshielded
wire
(maximum loop
resistance not to exceed
100 ohms)

Distance limitation
set by 100 ohm
resistance
limitation

12-18 AWG (3.25 - 0.75 mm

2

)

ANN-BUS
(EIA-485)
power-limited

Communication
for ANN-BUS
annunciator and
relay modules

Twisted pair a maximum
loop resistance of 120
ohms

6,000 (1,800 m)

12-18 AWG (3.25 - 0.75 mm

2

)

ANN-BUS
Power

Power for
ANN-BUS
annunciators

Refer to “ANN-BUS Devices” on page 33 for information on device wiring

24 VDC
Regulated,
resettable,
nonresettable

Power for
accessories and
4-wire devices

Untwisted, unshielded
wire

Distance limitation
set by 4 volt
maximum line
drop

12-18 AWG (3.25 - 0.75 mm

2

)

Auxiliary
Trouble Input

Open Collector
trouble input for
CHG-75,
CHG-120F, etc.

Single conductor

Distance limitation
20 feet in same
room

18 AWG (0.75 mm

2

)

NAC/Solenoid
Outputs

Connects to NAC
devices or
Release devices

Untwisted, unshielded
pair wire

Refer to Section F.1 on page 137.

Table F.1 FACP Wire Specifications