Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 53

MRP-2001 Series Manual — P/N 53040:D 12/15/2010
53
Master Programming Level
Programming
Pressing the down arrow key displays additional zone types as indicated in the following table.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
Zone Type
Action When Activated
Pull-Station
Fire Alarm
Manual Release
1
1 Activation of a Manual Release Switch will override Predischarge Delay, resulting
in an immediate water release.
Fire Alarm
N/A
Normally Open Contact
Fire
N/A
N/A
N/A
Waterflow
Fire
Waterflow NS (nonsilenceable)
Fire, nonsilenceable
Combo
Fire/Supervisory
Combo w/AutoResettable Superv
2
2 AutoResettable means that a device with this type code, when activated, will
automatically reset when the corresponding condition is cleared.
Fire/Supervisory, nonlatching
2-Wire Smoke
Fire Alarm
2-Wire Heat
Fire Alarm
N/A
Linear Heat
Fire Alarm
N/A
N/A
Fire
Fire Alarm
Low Pressure
Supervisory, latching
Low Pressure AutoResettable2
Supervisory, nonlatching
High Pressure
Supervisory
High Pressure AutoResettable2
Supervisory, nonlatching
Disable Release
3
3 Disable Release allows the installer to disable the releasing solenoids during
system testing. Disable Release will only work when the system is not in alarm.
Supervisory, nonlatching (disables Release Circuits)
Supervisory
Supervisory, latching
Supervisory AutoResettable2
Supervisory, nonlatching
N/A
2nd-Shot Water Switch
4
4 The 2nd-Shot Water Switch provides the option of performing another immediate
water release manually. Refer to “2nd-Shot Water Switch” on page 92.
Fire Alarm, nonlatching
Table 3.1 Zone Types