Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual

Page 15

background image

MRP-2001 Series Manual — P/N 53040:D 12/15/2010

15

Specifications

Product Description

Special Application Resettable or Nonresettable Power - TB9

Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:

Jumper pins 1 & 2 on JP31 for nonresettable power

Jumper pins 2 & 3 on JP31 for resettable power

Refer to the Device Compatibility Document for compatible listed devices

Special Application Primary ANN-BUS Power - TB3

Operating voltage: Nominal 24 VDC
Maximum Available Current: 500 mA
Power-limited circuit

Special Application Secondary ANN-BUS Power - ANN-SEC - TB1

Operating voltage: Nominal 24 VDC
Maximum Available Current: 500 mA
Power-limited circuit

The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP with the FLPS-7 power supply.

TB9

TB5

TB7

TB3

TB1

Figure 1.1 Current Availability

p

owe

rd

ist

mrp

.w

mf

Refer to the battery calculations
section for additional information.

Standby

1.0 amp max

per panel

Special Application

Nonresettable or

Resettable Power

Special Application

Resettable Power

NAC #1

NAC #2

NAC #3

NAC #4

0.5 amp max

per circuit

0.5 amp max

per circuit

3.0 amps max

per circuit

3.0 amps max

per circuit

3.0 amps max

per circuit

3.0 amps max

per circuit

Alarm

7.0 amps

max

per panel

Primary

ANN-BUS

Standby

1.0 amp max

per panel

0.5 amp max

per circuit

0.5 amp max

per circuit

ANN-SEC

Option Card