Coding, Coding 1=steady 2=march time 3=california, Coding 1=temporal 2=future use 3=future use – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 62: Coding 1=sync gentex 2=sync faraday 3=sync amseco

62
MRP-2001 Series Manual — P/N 53040:D 12/15/2010
Programming
Master Programming Level
will cause a screen to be displayed with the options 1=No Silence Inhibit and 2=1 Min. Silence
Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute
Silence Inhibit for the selected Output.
Coding
The Coding feature allows the programmer to select the type of output that the main circuit board
outputs will generate when activated. Pressing 1 while viewing Output Screen #3 will cause the
following displays to appear:
OUTPUT
#1=CODING
Output Screen #3
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=FUTURE USE
3=FUTURE USE
Coding Screen #2
CODING
1=CROSS ZONE
2=SYNC SYSTEM SENSOR
3=SYNC WHEELOCK
Coding Screen #3
CODING
1=SYNC GENTEX
2=SYNC FARADAY
3=SYNC AMSECO
Coding Screen #4