Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 59

MRP-2001 Series Manual — P/N 53040:D 12/15/2010
59
Master Programming Level
Programming
Pressing the down arrow key while viewing the Edit Output Type Screen will display additional
screens with the types shown below:
Release Circuit 1
Release Circuit 2
Alarm NAC
Waterflow NAC
Release Stage NAC
Horn NAC
Strobe NAC
Supv Bell NAC
Trouble Bell NAC
Press the number key corresponding to the desired Output Type to program the selected Output.
Release Circuit 1 or Release Circuit 2
If Release Circuit 1 or Release Circuit 2 is selected as the Output Type, the following subscreen
will be displayed:
This screen allows the programmer to select whether or not to supervise the Releasing Circuit
Output for shorts.
•
UNSUPV SHORTS - this option should normally be selected when a releasing solenoid is
connected to the output so the solenoid coil is not supervised for shorts
•
SUPV SHORTS - this option, which supervises for shorts, should only be selected when the
REL-4.7K option is installed in series with the solenoid coil
Release Stage NAC
If Release Stage NAC is selected as the Output Type, the following subscreen will be displayed:
EDIT RELEASE CIR #
1=UNSUPV SHORTS
2=SUPV SHORTS
NOTE:
Release circuits may be directly activated by a single input zone or may be activated
using cross-zoned inputs. Refer to “Circuit Mapping and Cross-Zoning” on page 105 for a
description of cross-zoning and input to output circuit mapping.
RELEASE STAGES
1=RELEASE 1 ONLY
2=RELEASE 2 ONLY