FACP Configuration Templates

Template 5: Single Hazard - 3 Zones and Low Pressure

FACP Relay Operation

The following description of FACP relay operations are in addition to normal system operation.

Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 (Water-
flow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull Station) will
operate Alarm Relay

Trouble Relay - any system trouble will activate the Trouble Relay

Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay

Device Installation Example for Template 5

Notes:

1. Waterflow Delay is programmed for 10 seconds.
2. All End-of-Line Resistors, illustrated in this example, are 4.7K

, ˝ watt (PN: 71252).

3. All devices are connected as Class B circuits. For details on connecting as Class A circuits,

refer to “CAC-5X Class A Converter Module” on page 29.

Output Circuit #1

Alarm NAC

Output Circuit #2

Waterflow NAC

1

Input Circuit #1
2-Wire Smoke

Input Circuit #2
Fire (Heats)

Input Circuit #3
Waterflow

1

Input Circuit #4
Manual Release

Input Circuit #5
Pull Station

Output

Circuit #4

Release

Solenoid 1

Output Circuit #3

Supervisory Bell

NAC

Input Circuit #6

Low Pressure