Timers, System setup 1=future use 2=timers 3=banner, Timers 1=ac loss delay 2 hr – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 67

MRP-2001 Series Manual — P/N 53040:D 12/15/2010
67
Master Programming Level
Programming
Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
Timers
Timers for Soak, Waterflow Delay and AC Loss Delay can be programmed by pressing 2 while
viewing System Setup Screen #1. The following screen will be displayed:
PROGRAMMING
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP
Programming Screen
SYSTEM SETUP
1=FUTURE USE
2=TIMERS
3=BANNER
System Setup Screen #1
SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND NO
3=CHARGR DISABLE NO
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPTION OFF
2=SEC ANN ENABLE NO
System Setup Screen #3
SYSTEM SETUP
1=FUTURE USE
2=TIMERS
3=BANNER
System Setup Screen #1
TIMERS
1=SOAK 1 10 MIN
2=SOAK 2 10 MIN
3=WATERFLOW DELAY 60S
Timer Screen #1
TIMERS
1=AC LOSS DELAY 2 HR
Timer Screen #2