MRP-2001 Series Manual — P/N 53040:D 12/15/2010

73

Master Programming Level

Programming

The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label, located on the FACP backbox door

When the ANN-80C LCD Canadian indicator is installed: Local Silence button will silence
annunciator piezos, Lamp Test button will perform an annunciator lamp test, pressing and
holding Sounder Test button will sound annunciator piezo, pressing step up/down arrows will
scroll through stored events. These buttons may be enabled or disabled by programming.

Secondary ANN-BUS Option

Pressing 2 while viewing System Setup Screen #3 allows the user to enable the secondary
ANN-BUS. The secondary ANN-BUS must be enabled if any modules are connected to the
ANN-SEC option card at J13. To enable the Secondary ANN-BUS, press 1 while viewing the
SEC-ANN screen so that the display reads SEC ANN Enabled Yes. Each press of the 1 key will
cause the display to toggle between SEC ANN Enabled Yes and SEC ANN Enabled No. The factory
default setting is ANN-SECONDARY Enabled No.

3.5.7 ANN-BUS

Optional ANN-BUS devices available for the FACP include annunciators, relay modules and
printer connection for acquiring hardcopy printouts of panel data. Pressing 1 while viewing
Programming Screen #3 will cause the control panel to display the following screens.

An ANN-S/PG Printer module, ANN-80 LCD annunciator module and ANN-RLY relay module
can be programmed in the FACP. These devices communicate with the FACP over the ANN-BUS
terminals on the control panel.

ANN-BUS Enabled

The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads ANN-
BUS Enabled Yes.
Each press of the 1 key will cause the display to toggle between ANN-BUS
Enabled Yes
and ANN-BUS Enabled No.

SYSTEM SETUP

1=CANADIAN OPTION
2=SEC ANN ENABLE

System Setup Screen #3

PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST

Programming Screen #3

ANN-BUS
1=BUS ENABLED NO
2=BUS MODULES
3=AUTO CONFIGURE

ANN-BUS Screen #1

ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS

ANN-BUS Screen #2