Banner, Ac loss delay range 00-24 hours, Select banner 1=factory banner 2=user banner – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 69: Factory banner press enter if ok
MRP-2001 Series Manual — P/N 53040:D 12/15/2010
69
Master Programming Level
Programming
AC Loss Delay
The reporting of a loss of AC power can be delayed by programming the length of the desired
delay. Press 1 while viewing Timer Screen #2 to display the following:
A flashing cursor will appear in the lower left corner of the display. The factory default setting is
02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When the
second digit is entered, the display will return to AC Loss Delay Screen #1.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause
the following to be displayed:
Pressing 1 while viewing the Select Banner Screen will display the following screen:
This screen allows the user to select the factory default Banner which will be displayed when the
system is in Normal Mode of operation. Press the Enter key to accept this as the default display.
Press the Escape key to cancel and return to the Select Banner Screen.
TIMER
1=AC LOSS DLAY 2 HR
Timer Screen #2
AC LOSS DELAY
RANGE 00-24 HOURS
AC Loss Delay Screen #1
NOTE: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC Loss
exist in the panel, the System Trouble relay will delay activation for the duration of the AC Loss
Delay setting.
SYSTEM SETUP
1=FUTURE USE
2=TIMERS
3=BANNER
System Setup Screen #1
SELECT BANNER
1=FACTORY BANNER
2=USER BANNER
Select Banner Screen
FACTORY BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1