6 supervisory operation, 7 disable/enable operation – Fire-Lite MRP-2001C PRE-ACTION/DELUGE CONTROL PANEL User Manual
Page 91

MRP-2001 Series Manual — P/N 53040:D 12/15/2010
91
Supervisory Operation
Operating Instructions
•
Second line in display:
control panel or custom entry via PC.
control panel or custom entry via PC.
•
Third line in display: Zone 1 indicates the zone programmed to this device which, in this
example, is Input Zone 1.
•
Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 03 for March, 08 for the 8th day of
the month and 09 for the year 2009
4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
•
The piezo sounder pulses ½ second On and ½ second Off
•
The Supervisory indicator flashes ½ second On and ½ second Off
•
The LCD displays the status label Active Supervisory along with the device name, type,
adjective/noun, associated zones and time/date
•
The output circuits programmed as Supervisory NAC are activated
•
The supervisory relay is activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
A typical Supervisory event would be displayed as illustrated in the following:
In the preceding example:
– FROZEN SUPRV - indicates zone detector is below approximately 45
o
F
Note that, like alarms, supervisory signals latch (except when programmed for supervisory
autoresettable). Supervisory alarms do not cause resound as do other alarm conditions. Open
circuits in supervisory wiring are processed by the control panel the same way as other trouble
conditions. Refer to “Alarm Operation” on page 90, for a description of the information displayed
on the control panel LCD.
4.7 Disable/Enable Operation
Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are
held in the off state. Disabled zones/NACs are treated as if they were in trouble, with the exception
being the LCD status label that will be displayed is DISABL.
FREEZE SUPERVISORY
ZONE 05 FROZEN SUPRV
10:00A 030806