Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Operating Instructions

Operation

4.4.9 Alarm/Alert Response, System Configured for Combo

Fire/Mass Notification with Fire Priority

If a fire alarm only occurs under this configuration, then the system will respond as in Section 4.4.3

above.
If a mass notification alarm/alert only occurs under this configuration, then the system will respond

as in Section 4.4.7 above and additionally will:

• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can

annunciate the alarm/alert and notify a central station (if programmed to do so).

If a fire alarm is active in the system and a subsequent mass notification alarm/alert occurs, then the

system will not respond until the fire alarm has been restored.

4.4.10 Alarm/Alert Restoral, System Configured for Combo

Fire/Mass Notification with Fire Priority

If the restoral is for a fire alarm only under this configuration then the system will respond as in

Section 4.4.4 above.
If the restoral is for a mass notification alarm/alert only under this configuration then the system

will respond as in Section 4.4.8 above and additionally will:

• Signal the FACP of the restoral using the FACP Data Bus such that the FACP can stop

annunciation of the alarm/alert and notify a central station (if programmed).

If the restoral is for a fire alarm that overrode an earlier active mass notification alarm/event then

the system will:

• Stop playing the fire alarm message
• Turn the “Fire System Active” LED off
• Return the system to the active state of the earlier mass notification alarm/event

4.4.11 Alarm/Alert Response, System Configured for Combo

Fire/Mass Notification with Mass Notification Priority

If a fire alarm only occurs under this configuration then the system will respond as in Section 4.4.3

above.
If a mass notification alarm/alert only occurs under this configuration then the system will respond

as in Section 4.4.7 above. and additionally will:

• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can

annunciate the alarm/alert and notify a central station (if programmed to do so).

If a fire alarm is active in the system and a subsequent mass notification alarm/alert occurs, then the

system will:

• Stop playing the current fire message
• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can

annunciate the alarm/alert, notify a central station (if programmed), and turn off audible

NACs (if programmed).

• Respond as in Section 4.4.7 above

If a mass notification alarm/alert is active in the system and a subsequent fire alarm occurs, then the

system will not respond until the mass notification alarm/alert is restored.