beautypg.com

Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 50

background image

50

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Installation

Installation of Option Modules

4. Plug the supplied power cable into J10 on the main control board, then into J1 on the audio

amplifier. Plug the supplied control cable into J11 on the main control board, then into J2 on

the audio amplifier.

5. Configure the slide switches, SW6 and SW7, per Figure 2.35. Do not use any other setting.
6. Configure the slide switch, SW5, on the main control board for 25V or 70V operation. (70V

operation requires Amplifier model ECC-50W-70V and the ECC-XRM-70V transformer.)

7. Connect field wiring to TB21 on the main control board (if not using the amplifier as backup).

Refer to Figure 2.15 on page 36 for illustration of speaker connections if the amplifier is being

used to expand system power to 100 watts (providing dual 50 watt speaker circuits).

8. Configure the Audio Amplifier for primary or backup amplifier operation through the web-

based programming utility.

J12

TB15

J9

+-

RTZM

Rev.

ECC-MCB-PCA

Figure 2.32 Installation of the Optional Audio Amplifier

ECC-50W-25/70V

ECC-50/100

main control board

b

d

a

m

n

t.

w

m

f

LED4 - Fault

LED2 - Limit

LED3 - Enabled

SW4 - Fail Test Switch

SW7 - 35W - NOT USED

SW6 - 50W

SW5 - 75W

(Not populated on 70V boards) -

NOT USED

LED1 - Power

BDA

Power

BDA

Control

Connect J1 to J10

Connect J2 to J11

This manual is related to the following products: