Programmed Activation by FACP

The default setting is No Message for each speaker circuit. In the screen shown above, Z32 is the

zone dedicated for all speaker circuits. To change from No Message, press 3 to display the follow-

ing screens:

Select the message (Message 1 through Message 14) by pressing the number corresponding to the

desired message. After the selection is made, the display will return to the screen displaying Z32

which will have changed from No Message to the selected message.
Repeat the procedure outlined above for each speaker zone (Z32 through Z56) and then exit Pro-

gramming by pressing the Escape (ESC) key to save the programming changes. Test the system to

ensure proper operation.