beautypg.com

Acs mode wiring – Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 40

background image

40

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Installation

Output Circuits

ACS Mode Wiring

When communication is wired over the ACS annunciator link, a monitor module must be used to

monitor mass notification events. Wire the monitor module to the ECC at TB1 MNS Active Relay

in addition to the Data Bus wiring shown above. Refer to the FACP manual for information on type

IDs.

SLC

TB1 MNS Active Relay

monitor
module

Figure 2.21 Monitor Module Wiring for ACS Communication

a

c

s

m

o

n

it

o

r.

w

m

f

This manual is related to the following products: