4 auxiliary dc power output connections, 5 input/initiating circuits, 1 cmd inputs – Fire-Lite ECC-50/100E Emergency Command Center User Manual
Page 32: Auxiliary dc power output connections, Input/initiating circuits, Cmd inputs
32
Emergency Command Center Manual —
P/N LS10001-000FL-E:A 4/10/2013
Installation
Auxiliary DC Power Output Connections
2.4 Auxiliary DC Power Output Connections
The Special Application Auxiliary DC power output is power-limited (Class 2).
2.5 Input/Initiating Circuits
2.5.1 CMD Inputs
The ECC-50/100 has eight Command Input circuits, which are used to activate the panel amplifiers
which, in turn, transmit an audio signal over the system speakers. All field wiring for the circuits is
power-limited (Class 2) and supervised for opens and ground faults. Note that zero impedance to
ground will cause a ground fault.
CMD1 and CMD2 Command Input circuits can be independently field programmed to be triggered
by a contact closure or by the reverse polarity of a Notification Appliance Circuit.
IMPORTANT! When CMD1 and CMD2 are configured for reverse polarity, the NAC cannot be
Coded (including NAC Sync).
CMD1 has internal relay contacts before the out terminals which will open the outgoing NAC cir-
cuit during an ECC-50/100 trouble condition (AC loss is programmable as described in Section 3).
This causes a NAC trouble at the host FACP. Note that CMD1 and CMD2 configurations can be
independently set so that both circuits are triggered by the same type of input or by different types
of inputs (see Figure 2.9 below).
TB17
Special Application Power (500 mA @ 24 VDC) is nonresettable power suitable
for powering control modules and End-of Line Power supervision relays.
See Device Compatibility Document for compatible devices.
Figure 2.8 Auxiliary Power Connection
e
c
c
tb
1
7
.w
m
f
Figure 2.9 Command Input Circuits
Style Z (Class A)
FACP ELR
(for Style Y - Class B only)
NAC reverse polarity trigger
(alarm polarity shown)
Class B (Style B) Contact Closure trigger input, such as
an emergency signaling manual pull station (MNS only).
(4.7K, 1/2 watt EOL Resistors P/N: 71252)
ECC-50/100 Main Control Board
e
c
c
tb
4
.w
m
f
alarm polarities shown
Host FACP
NAC
TB4
CMD1
TB5
CMD2
TB6
CMD3,4
TB7
CMD5,6
TB8
CMD7,8