ECC-50/125DA Distributed Audio Amplifier

2.10 ECC-50/125DA Distributed Audio Amplifier

SW2 on the ECC-50/100’s display board must be set to the UP position if any ECC-50/125DAs are

installed on the system. Refer to the ECC-50/125DA Distributed Audio Amplifier Manual,

LS10027-000FL-E, for installation instructions.

2.11 Shielding for External Device Wiring

The external data bus and external audio riser circuits must be wired using twisted, shielded pair

cable. Do not run either cable adjacent to or in the same conduit as 120 VAC service, noisy electri-

cal circuits that are powering mechanical bells or horns, speaker circuits, motor control circuits or

SCR power circuits. External operator interface power (24VDC) may be run adjacent to or in the

same conduit as the external data bus and external audio riser circuits.
At the ECC-50/100 unit, the cable shields must be connected to the same connectors where the sig-

nals originate. If only one external device (i.e. an ECC-RM) is used in the system, the shield in the

external device must be left floating. It must not touch anything. If multiple external devices are

used in the system then the shields must “pass through” (connect to the outgoing shield using wire

nuts without touching anything else). For Class A (Style Z) installations, the shield from the last

external operator interface must be connected to the same ECC-50/100 terminal that the shield

originated from.

NOTE: Never use a cable shield as an enclosure's earth ground. The EIA-485 shield is for
radiated noise emission protection (RFI, EMI).Refer to the following illustrations for details on
shield termination.

ECC-50/100

ECC-50/100

ECC-RM

ECC-RPU
ECC-LOC

ECC-50DA

ECC-125DA

ECC-RM

ECC-RPU
ECC-LOC

ECC-50DA

ECC-125DA

Class B
(Style Y)

Class A
(Style Z)

External Data Bus or

External Audio Riser

External Data Bus or

External Audio Riser

Figure 2.28 Shielding for One External Device