2 general/nac options, General options, General/nac options – Fire-Lite ECC-50/100E Emergency Command Center User Manual
Page 60
60
Emergency Command Center Manual —
P/N LS10001-000FL-E:A 4/10/2013
Programming
Main Menu - User Programming
Log Out
When all programming has been successfully completed, the user must log out to allow
the system to reboot and apply the programming changes.
3.1.2 General/NAC Options
General Options
Unit Operation
Select whether the ECC will function for Fire Evacuation, Mass Notification, or
a Combination of both.
Event Priority
When Combo or Mass Notification is selected for Unit Operation, select whether
Mass Notification
events or Fire Evacuation events will take priority in the system. If Mass Notifi-
cation
is selected as the Unit Operation with the Event Priority set to Fire Evacuation, the ECC will
be a mass notification only system but will allow the FACP to override it if a fire alarm sounds. If
Mass Notification
is selected as the Unit Operation with the Event Priority also set to Mass Notifi-
cation
, the ECC will not have any fire evacuation capabilities and will report mass notification
events to the FACP. In this configuration, FACP outputs can be turned off for mass notification
events if desired.
FACP Data Bus Control
If an FACP will directly communicate with the ECC, select which
communication protocol will be used, ACS-Bus or ANN-Bus.
FACP Data Bus Address This field has no effect on programming and is used for informa-
tional purposes only.
When using the FACP ACS-bus protocol, address 01 must be enabled in the
FACP programming. When using the ANN-Bus protocol, the FACP will automatically detect the
audio system connection during annunciator auto-configuration. No ANN-Bus address selection is
necessary at the FACP. Enter the ECC’s address (1-8) here. If FACP control of the ECC is not
selected, enter 0.
24 Hour Resound
As enabled (default), the 24 Hour Resound feature causes the piezo on the
ECC to sound a reminder ‘beep’ for alarms and troubles after the panel has been silenced.
Class A / Style Z
Select enable if all circuits on the ECC will operate in Class A (Style Z) or dis-
abled
if all circuits will operate in Class B (Style Y).
AC Loss Delay
The reporting of a loss of AC power using the AC Loss relay output can be
delayed by programming the length of the desired delay. The factory default setting is 2 hours.
Options are 0, 2, 6, 12, or 23 hours.
Secondary Amplifier
if an ECC-50W-25/70V is installed, select whether it will be used as a
backup
amplifier or for secondary speaker circuits. If an ECC-50W-25/70V is not installed, select
none
.
Figure 3.3 General Options