beautypg.com

Fire-Lite ECC-50/100E Emergency Command Center User Manual

Page 16

background image

16

Emergency Command Center Manual —

P/N LS10001-000FL-E:A 4/10/2013

Product Description

Input/Output Circuit Specifications

FACP Data Bus (EIA-485) - TB13, Terminals 1 (B IN), 2 (A IN), 3 (B OUT), & 4 (A OUT)

Dedicated connection to FACP serial bus

Output terminals: pass-through to other system components

Isolated, supervised

Minimum isolation withstand voltage: 1500 V

RMS

Maximum wiring impedance: 40  (ANN-BUS)/26  (ACS BUS)

External Audio Riser TB22, Terminals 1 (OUT+), 2 (OUT-), 4 (IN+), 5 (IN-), & 3 (SHLD)

Style Y (Class B) or Style Z (Class A) audio connections to external operator interface components

Power-limited (Class 2) circuitry, supervised

Audio signal level: 3.85 V

RMS

, maximum

Frequency range: 800 - 2,800 Hz

Frequency range (ECC-50/125DA): 800 Hz - 2.8 KHz

NOTE: Zero impedance to ground will cause a ground fault.

This manual is related to the following products: