5 programmed activation by facp, 1 ms-9600(ud)ls and ms-9200udls, Programmed activation by facp – Fire-Lite ECC-50/100E Emergency Command Center User Manual
Page 75: Ms-9600(ud)ls and ms-9200udls
Emergency Command Center Manual —
P/N LS10001-000FL-E:A 4/10/2013
75
Programmed Activation by FACP
Programming
3.5 Programmed Activation by FACP
The table below defines the capabilities for the FireLite FACPs that can automatically trigger the
audio system using the audio system’s “FACP Data Bus”. The FACP annunciator bus serves as
“FACP Data Bus” to the audio system. Note that automatic triggering capability is dependent upon
the FACP model, FACP version, and which annunciator bus protocol is used.
When using the FACP ACS-bus protocol, address 01 must be enabled in the FACP programming.
(Refer to the FACP user manual.) When using the ANN-Bus protocol, the FACP will automatically
detect the audio system connection during annunciator auto-configuration. No ANN-Bus address
selection is necessary at the FACP.
Once the FACP can communicate with the audio system, FACP zones Z33 through Z56 become
dedicated as output zones for speaker circuits 1 through 24 respectively. FACP zone Z32 is dedi-
cated to turn on all speaker circuits. FACP programming allows association between any address-
able SLC input device (module, detectors) with any of the speaker circuits. In addition, 1 of 14
messages can be generated over the selected speaker circuit.
Any fault in the audio system is sent to the FACP via the FACP Data Bus and is indicated as an
annunciator fault on the FACP display.
Column Descriptions for Table 3.2:
•
FACP
- the Fire Alarm Control Panel being used
•
Individual Audio Zone Control via FACP Data Bus
- ACS or ANN-BUS compatible FACPs
can control each audio zone on the ECC-50/100 (refer to Section 3.5.1.)
•
Individual Control of All Messages
- control of all voice messages in the ECC-50/100 can be
accomplished through the FACP Data Bus or by triggering the CMD inputs (refer to
•
Simultaneous Activation of All Audio Zones
- this is a single trip mechanism via a zone on the
FACP Data Bus or CMD input trigger that activates all the audio zones at the same time (refer
to Section 3.5.1.)
3.5.1 MS-9600(UD)LS and MS-9200UDLS
Important Notes:
1. For proper operation, a message must be assigned to each FACP zone that is programmed to
activate an audio speaker circuit.
2. The message repeat setting on the ECC-50/100 should be set to infinite. This will ensure that
lower priority activated zones will continue to broadcast the voice message.
3. CMD inputs are not used for activation when the FACP Data Bus is being used, however,
4.7K ELRs must still be connected across CMD3 - CMD8.
FACP
Individual
Audio
Zone Control
via
FACP Data Bus
Individual Control of
All Messages
Simultaneous
Activation of All
Audio Zones
ACS
ANN
ACS
ANN
CMD
MS-9600LS version 4 or higher
Yes
Yes
Yes
Yes
Yes
Yes
MS-9200UDLS version 2 or 3
Yes
No
Yes
No
Yes
Yes
MS-9200UDLS version 4 or higher
Yes
Yes
Yes
Yes
Yes
Yes
Table 3.2 FACP Message/Zone Control Capability