Input/Output Circuit Specifications
Product Description
Current Availability
The following figures illustrate the maximum current possible for each panel output circuit and the
total output current available from the power supply. Refer to Section 6, “Power Supply Calcula-
tions” for additional current draw by option cards that must be considered when determining total
standby and alarm currents.
TB20
TB21
TB19
TB24
TB23
TB17
Primary 50W
Speaker Circuit
3.3 amps max.
Secondary 50W
Speaker Circuit-
Optional Amplifier
Installed
3.3 amps max.
NAC Circuit
2.0 amps max.
Aux. Power
0.5 amp max.
Speaker Volume
Control Override
0.25 amp max.
External Operator
Interface Power
0.8 amp max.
Standby
2.0 amps max.
(includes background
music) with external
charger. Refer to
Alarm
7.5 amps
max.
Figure 1.2 Current Availability - 100 Watt System