Flow - Utilities Menu - Manual Test Mode 7.2

Page 66

MULTI-PARAMETER TRANSMITTER USER’S MANUAL

Flow - Utilities Menu - Manual Test Mode 7.2

DOWN

DOWN

DOWN

UP

DOWN

NOTE:

When the user exits the Manual Test Mode, the 4-20mA

output will remain in the Test Mode state until the operator

enters the run mode. The output will then revert back to

the previous On-line state.

The 4-20 mA output will track the
change in process value

RUN MODE

UP

NOTE

PRESS THE AND KEYS

TOGETHER TO GO IMMEDIATELY BACK TO

RUN MODE

DOWN

Press the key once
which will move the cursor
over the least digit of the
simulated process value.

Use the and keys to change
the simulated process value.

Manual Test Mode is used to simulate a process reading
in order to verify the correct response of the output.
When in the Manual Test Mode, the output is no longer
placed on hold as it is when in the rest of the menu.

Press the key once to
move the cursor to the RH side
of the display

Press the key to return to the
MANUAL TEST MODE menu

The 4-20 mA output will follow the process
value change.

DOWN

UP

DOWN

MANUAL TEST MODE

TOTAL 0

CALIBRATION

UTILITIES

TEST 65.00 GPM >

TEST 65.0 0 GPM >
14.4mA

14.4mA

TEST 65.0 0 GPM >

TEST 50.0 0 GPM >

TEST 50.00 GPM >
12.0mA

12.0mA

14.4mA

DOWN