Flow - Calibration Menu - K Factor 7.1

Flow - Calibration Menu - K Factor 7.1

Page 65

DOWN

DOWN

DOWN

DOWN

UP

DOWN

DOWN

The K Factor menu is used to enter the flow sensor calibration factor. The K Factor represents the number of pulses
per U.S. Gallon, generated by the combination of sensor and flow fitting.
It is normally stamped on the flow fitting or attached to a tag on the cable. Typical K factors range between 0.5000 to
1500.0.

If the calibration did not appear
to be correct, press the
key which will return back to the
K Factor menu without storing
the value.

DOWN

NOTE:
ACCELERATOR KEYS
Pressing the or
key once will change the
value by the smallest digit.
Holding the key down will
cause the to value change at
an increasing rate until the
key is released. Pressing the
key again will cause the value
to start changing at it's
slowest rate again. This
allows the user to get to the
new K Factor value quickly.

DOWN

UP

The K Factor can be set
anywhere from 0.5000 pulses
per U.S.Gallon to
1500.0 pulses per U.S.Gallon

RUN MODE

Press to store the
calibration data and return
back to the menu so the user
can select another function.

UP

NOTE

PRESS THE AND KEYS

TOGETHER TO GO IMMEDIATELY BACK TO

RUN MODE

DOWN

DOWN

Press the key to accept the
change and move to the store function

Use the and keys to
adjust the reading until it agrees with
the actual K Factor as specified on
the sensor

If the K Factor setting is OK, use the
key to move the cursor over the Y text and
press the down key.

DOWN

To enter the K factor, use the
key to enter the Calibration menu
and then the key to select the
K Factor menu.

DOWN

Then press to move
the cursor to the RH position

UP

DOWN

If you just wish to view the
current K Factor without
changing it, press the
key which will move to the
store function

DOWN

Press the key once
which will move the cursor
over the least sign. digit of
the display.

TOTAL 0

CALIBRATION

K FACTOR

STORE?

Y N

STORE?

Y N

K FACTOR

K FACTOR

K FACTOR

K FACTOR
125.00

>

125.0 0

>

100.0 0

>

K FACTOR

100.00

>

K FACTOR