beautypg.com

Introduction – A.O. Smith HW 610 User Manual

Page 7

background image

7

INTRODUCTION

This design complies with the current edition of the ANSI Z21.13

low-pressure boiler standard.

Compliance under this standard implies that when the boiler

underwent test, the gas manifold and control assembly pro vided

on the boiler met safe lighting and other performance criteria.

Detailed installation diagrams are found in this manual. These

diagrams will serve to provide the installer a reference for the

materials and methods of piping necessary. It is essential that

all water, gas piping and wiring be installed as shown on the

diagrams. You should thoroughly read and understand this manual

before installation and/or operation of this boiler.

The factory warranty will be void if the boiler(s) have been

improperly installed or operated.

In addition to these instructions, the boiler(s) shall be installed

in accordance with those installation regulations in force in the

local area where the installation is to be made. These shall be

carefully followed in all cases. Authorities having jurisdiction

should be consulted before installations are made.

In the absence of local codes, the installation must comply with the

current editions, as follows:

In the United States:

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the

National Electric Code, NFPA 70.

In Canada:

Installation Code CAN/CSA B149.1 and Canadian Electrical Code,

CSA C22.1.

GROUNDING INSTRUCTIONS

This boiler must be grounded in accordance with the National Electrical

Code, Canadian Electrical Code and/or local codes. Correct wiring is

imperative for proper operation.

This boiler must be connected to a grounded metal, permanent

wiring system, or an equipment grounding conductor must be run

with the circuit conductors and connected to the equipment grounding

terminal or lead on the boiler.

CORRECT GAS

MAKE SURE THE GAS ON WHICH THE BOILER WILL

OPERATE IS THE SAME AS THAT SPECI FIED ON THE

BOILER RATING PLATE. DO NOT INSTALL THE BOILER IF

EQUIPPED FOR A DIFFERENT TYPE OF GAS — CONSULT

YOUR SUPPLIER.

PRECAUTIONS

IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT

OPERATE UNTIL ALL CORRECTIVE STEPS HAVE BEEN

MADE BY A QUALIFIED SERVICEMAN:

1. EXPOSURE TO FIRE.

2. IF DAMAGED.

3. FIRING WITHOUT WATER.

4. SOOTING.

IF THE BOILER HAS BEEN EXPOSED TO FLOODING, IT

MUST BE REPLACED.

LIQUEFIED PETROLEUM GAS MODELS

Boilers for propane or liquefied petroleum gas (LPG) are different

from natural gas models. A natural gas boiler will not function

safely on LP gas and no attempt should be made to convert a

boiler from natural gas to LP gas.

LP gas must be used with great caution. It is highly

explosive and heavier than air. It collects first in the low

areas making its odor difficult to detect at nose level.

If LP gas is present or even suspected, do not attempt

to find the cause yourself. Leave the building, leaving

doors open to ventilate, then call your gas supplier or

service agent. Keep area clear until a service call has

been made.

At times you may not be able to smell an LP gas leak.

One cause is odor fade, which is a loss of the chemical

odorant that gives LP gas its distinctive smell. Another

cause can be your physical condition, such as having

a cold or diminishing sense of smell with age. For

these reasons, the use of a propane gas detector is

recommended.

IF YOU EXPERIENCE AN OUT OF GAS SITUATION, DO

NOT TRY TO RELIGHT APPLIANCES YOURSELF. Call

your local service agent. Only trained LP professionals

should conduct the required safety checks in accordance

with industry standards.

HIGH ALTITUDE INSTALLATIONS

Rated inputs are suitable up to 2000 feet (610 m) elevation.

Consult the factory for installation at altitudes over 2000

feet (610 m).