2. LINEAR-TEMP INSTALLATIONS

Control for these systems is decided mainly by the type of building

system controlling that is desired. A single boiler installation might

be controlled directly from space temperature thermostat(s).

Multiple boiler installations are more effective when the boilers are

sequenced in and out of operation by some form of main water

temperature controller. With one to three boilers, individual controls

set at progressive temperatures may be used. For more than three

or four boilers, a step controller is recommended.

Individual boiler controls, or the separate stages of a step controller,

should fire a boiler and also start the boiler loop circulator whenever

the first boiler of a group supplied by that boiler loop is fired. Some

large installations may require the firing of more than one boiler

per stage.

The system or primary circulator may or may not be controlled

by the boiler sequencer. When this pump is operated through

the first switch of any type of step controller, care should be

taken to determine if a motor starter is needed due to insufficient

switch capacity.

If the primary pump is controlled by a manual switch or any other

controllers, the electric current supply to the boiler group should

be through the primary pump controller. The fast response of

A. O. Smith boilers eliminates any need to maintain boiler

temperature when the system is satisfied. Wiring should always

prevent firing of boiler(s) when there is no water flow in the mains.

Installation diagrams show flow switches in the outlet piping from

each boiler as good protection against any boiler being fired when

the boiler loop circulator is not in operation. These flow switches

will also serve as protection if there is a loss of water.

Outdoor vent systems will normally require an automatic shutdown

control if there is a continuous recirculating main and/or if the entire

building is not under control of space temperature thermostats. A

single bulb outdoor sensing control will prevent overheating of halls,

stairways or other uncontrolled areas. There are occasions when

outdoor temperatures are temporarily too warm for even a moderate

amount of heating in these areas.

Space temperature controlling can be varied to meet the building

requirements. Either the single thermostat, as shown, or multiple

zone thermostats should control a common relay. This relay

controls electric power to the system primary circulator and

to the main water temperature controller. This provides for

water movement in the system before the main temperature

controller can start the secondary circulating pump or fire

the boiler.

Figure 17 shows a typical wiring diagram for a single boiler space

heating installation. The boiler may be controlled by a main

temperature controller as shown or may include outdoor reset

if desired.

Figure 18 on page 26 shows a layout for various choices of controls

often found in commercial heating. These layouts are not intended

to be wiring diagrams and only show the relation of one device to

another in the system.

Figure 18 is a typical layout of controls for two boilers with one

circulator and including optional outdoor reset and thermal balancer.

If a secondary circulator is used with each boiler, arrangement for

boiler no. 2 will be as shown for boiler no. 1.

Commercial size installations are always best when designed to

individual building requirements.

The layout in figure 18 is typical of many combination possibilities to

meet the requirements of different buildings. Brand names of controls

shown are suggestions and not directly related to any particular type

of system. THESE LAYOUTS ARE NOT WIRING DIAGRAMS.

TYPICAL WIRING DIAGRAM (IID SYSTEM) FOR SINGLE BOILER LINEAR-TEMP

®

INSTALLATION

FIGURE 17.