THREE HW-520's, HW-610's OR HW-670's UP-FLOW MODEL

COMMERCIAL BOILER WITH HORIZONTAL TANK, CER-TEMP 80

IMPORTANT

THE INSTALLATION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED

TO PROTECT THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR

CIRCULATOR FAILURE.

+ PIPING AND FITTINGS BETWEEN GATE VALVES AND BOILERS SHOULD BE

BRASS OR BRONZE. OTHER PIPING SHOULD CONFORM TO LOCAL CODES.

GATE VALVES ARE SHOWN FOR SERVICING BOILER. HOWEVER, LOCAL CODES

SHALL GOVERN THEIR USAGE.

* PRESSURE RELIEF VALVE RATING SHOULD NOT EXCEED PRESSURE

CAPACITY OF ANY COMPONENT IN THE SYSTEM.

** INSTALL THERMOMETER AND PRESSURE RELIEF IN OPENINGS PROVIDED

ON HW-520, HW-610 & HW-670.

WIRING - FIGURES 21 to 27 on

pages 28 to 32.

HEATERS SPACED 24" APART

INSTALL IN ACCORDANCE

WITH ALL LOCAL CODES

FIGURE 33.

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT

FIXTURES. SEE TANK TEMPERATURE CONTROL WARNING. IF HIGHER PREHEAT

TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT,

ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.

USE THIS TABLE FOR CORRECT

PUMP AND WATER PIPE SIZE

Model

Number

Minimum

Pipe Size

(Inches)

B & G

Pump

Size

*Armstrong

Pump Size

A

B

HW-520

2-1/2"

1-1/2"

2"

S-45 2-1/2"

HW-610/670

3"

1-1/2"

3" HD-3

S-46

* Assumes 50 equivalent feet of piping or less.