Adjustment, if required, is performed as follows:

1. Set primary system temperature control dial (thermostat) at

lowest setting so that boiler will not call for heat.

2. Attach a pressure gauge to the tapping in the control string

elbow.

3. Reset primary system temperature control dial (thermostat) to

highest setting. Main burner will now ignite.

4. With main burner firing, adjust pressure, if necessary, by turning

pressure regulator adjusting screw with a screwdriver.

• Clockwise to increase pressure.

• Counterclockwise to decrease pressure.

5. Set primary system temperature control dial (thermostat) to

lowest setting.

6. Remove pressure gauge and replace sealing plug.

7. Set primary system temperature control dial (thermostat) to

desired setting.

WARNING

DO NOT INCREASE GAS PRESSURE ABOVE THAT SPECIFIED

ON THE RATING PLATE, AS OVERFIRING WILL RESULT IN

DAMAGE TO THE BOILER, AS WELL AS INCREASED RISK

OF FIRE, SOOTING AND ASPHYXIATION.

If gas pressure regulator cannot be adjusted to correct pressure with

sufficient gas pressure at the valve, replace with new gas valve.

WIRING

WIRING CONNECTIONS

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN

SERVICING CONTROLS. WIRING ERRORS CAN CAUSE

IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER

OPERATION AFTER SERVICING.

1. CONVENTIONAL INSTALLATIONS

ALL ELECTRICAL WORK MUST BE INSTALLED IN ACCORDANCE

WITH NATIONAL ELECTRICAL CODE, ANSI/NFPA 70 AND/

OR THE CANADIAN ELECTRICAL CODE, PART 1, CSA C22.1,

ELECTRICAL CODE AND MUST CONFORM TO LOCAL

REGULATIONS.

The boiler, when installed, must be electrically bonded to ground in

accordance with the requirements of the authority having jurisdiction

or, in the absence of such requirements, with the National Electrical

Code, ANSI/NFPA 70 and/or the Canadian Electrical Code Part 1,

CSA C22.1, Electrical Code.

STRICT ADHERENCE TO PIPING AND WIRING DIAGRAMS IS

REQUIRED TO PREVENT CONSTANT PUMP OPERATION WHEN

SYSTEM TEMPERATURE CONTROL IS SATISFIED. OTHERWISE

THE WARRANTY IS VOID AS STIPULATED IN THE LIMITED

WARRANTY ON THE INSTRUCTIONS MANUAL.

The electrical connections must be made so that the circulator will

operate before the gas valve opens. At no time may the controlling

system allow the burner to fire when there is no water flow through

the boilers.

Refer to the diagrams in Figures 16 and 17 on pages 24 and

25 for proper wiring sequence with conventional single boiler

installations.

The THERMAL BALANCER shown is factory included by

A. O. Smith. This device serves as a pump shutdown delay switch to

balance the rising boiler water temperature to system temperature

before the pump stops. Overshooting of boiler temperature is

prevented and stack loss after shutdown is negligible.

WARNING

AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF

ELECTRIC SHOCK OR POSSIBLE ELECTROCUTION. Make the

ground connection to the screw provided in the electrical supply

junction box on the boiler.

IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED WITH THE

APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED

WITH TYPE 105

0

C WIRE OR ITS EQUIVALENT, EXCEPT FOR

THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250

0

C

AND WIRES CONNECTED TO THE COIL PROTECTOR WHICH

ARE 200

0

C.