beautypg.com

A.O. Smith HW 610 User Manual

Page 13

background image

13

PERMIT OPERATION OF GAS APPLIANCES IF INSTALLED

18 INCHES OR MORE ABOVE THE FLOOR. THIS MAY

REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT

BE AVOIDED.

WARNING

FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY

OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST

NEVER BE PLACED ON OR ADJACENT TO THE BOILER.

OPEN CONTAINERS OF FLAMMABLE MATERIAL MUST

NOT BE STORED OR USED IN THE SAME ROOM WITH

THE BOILER.

A hot water boiler installed above radiation level or as required

by the authority having jurisdiction, must be provided with a low

water cutoff device at the time of boiler installation.

AIR REQUIREMENTS

Provisions for combustion and ventilation air in accordance

w i t h t h e c u r r e n t e d i t i o n o f t h e N a t i o n a l F u e l G a s

Code, ANSI Z223.1, CAN/CSA B149.1, Installation

C o d e s , o r a p p l i c a b l e p r o v i s i o n s o f t h e l o c a l

building codes.

Provisions for vent, bleed and gas relief lines (when applicable).

Keep appliance area free of combustible or flammable liquids.

Do not obstruct the flow of combustion or ventilating air.

WARNING

FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR

COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPLY

OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION

PRODUCTS RESULTING IN AIR CONTAMINATION THAT

MAY BE HAZARDOUS TO LIFE. SUCH A CONDITION OFTEN

WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME,

CAUSING CARBONING OR SOOTING OF THE COMBUSTION

CHAMBER, BURNERS AND FLUE TUBES AND CREATES A

RISK OF ASPHYXIATION.

Unconfined Space

In buildings of conventional frame, brick or stone construction,

unconfined spaces may provide adequate air for combustion, and

draft hood dilution.

If the unconfined space is within a building of tight construction

(buildings using the following construction: weather stripping,

heavy insulation, caulking, vapor barrier, etc.) air for combustion,

ventilation, and draft hood dilution must be obtained from

outdoors or spaces freely communicating with the outdoors. The

installation instructions for confined spaces in tightly constructed

buildings must be followed to ensure adequate air supply.

Confined Space

(a) U. S. Installations

When drawing combustion and dilution air from inside a conventionally

constructed building to a confined space, such a space shall be

provided with two permanent openings, ONE WITHIN 12 INCHES

OF THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES OF THE

ENCLOSURE BOTTOM. Each opening shall have a free area of at

least one square inch per 1000 Btuh of the total input of all appliances

in the enclosure, but not less than 100 square inches.

If the confined space is within a building of tight construction,

air for combustion, ventilation, and draft hood dilution must be

obtained from outdoors. When directly communicating with the

outdoors or communicating with the outdoors through vertical

ducts, two permanent openings, located in the above manner,

shall be provided. Each opening shall have a free area of not

less than one square inch per 4000 Btuh of the total input of

all appliances in the enclosure. If horizontal ducts are used,

each opening shall have a free area of not less than one

square inch per 2000 Btuh of the total input of all appliances

in the enclosure.

(b) Canadian Installations

Ventilation of the space occupied by the boiler(s) shall be

provided by an opening for ventilation air at the highest practical

point communicating with outdoors. The total cross-sectional

area shall be at least 10% of the area of the combustion air

opening but in no case shall the cross-sectional area be less

than 10 square inches (6500 mm

2

).

In additional to the above, there shall be permanent air supply

opening(s) having a cross-sectional area of not less than 1

square inch per 7,000 BTUH (310 mm

2

/KW) up to and including

1,000,000 BTUH plus 1 square inch per 14,000 BTU in excess

of 1,000,000 BTUH. This opening(s) shall be located at, or

ducted to, a point neither more than 18" (450 mm) nor less

than 6 inches (150 mm) above the floor level.

Where power vented equipment is used in the same room as the

boiler, sufficient air openings must be supplied.

UNDERSIZED OPENINGS MAY RESULT IN INSUFFICIENT AIR

FOR COMBUSTION.

WHERE AN EXHAUST FAN IS INSTALLED IN THE SAME ROOM

WITH A BOILER, SUFFICIENT OPENINGS FOR AIR MUST BE

PROVIDED IN THE WALLS.

UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN

INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR

COMBUSTION. SOOTING MAY RESULT WITH AN INCREASED

RISK O F ASPHYXIATION.

CHEMICAL VAPOR CORROSION

WARNING

CORROSION OF THE FLUEWAYS AND VENT SYSTEM

MAY OCCUR IF AIR FOR COMBUSTION CONTAINS

C E R T A I N C H E M I C A L V A P O R S W H I C H B R E A K

DOWN INTO ACIDS AT HIGH TEMPERATURE. SUCH

CORROSION MAY RESULT IN FAILURE AND RISK OF

ASPHYXIATION.

Water boiler corrosion and component failure can be caused

by the heating and breakdown of airborne chemical vapors.

Spray can propellants, cleaning solvents, refrigerator and air

conditioning refrigerants, swimming pool chemicals, calcium

and sodium chloride, waxes, and process chemicals are typical

compounds which are corrosive. These materials are corrosive

at very low concentration levels with little or no odor to reveal

their presence. Products of this sort must not be stored near

the boiler. Also, air which is brought in contact with the water

boiler should not contain any of these chemicals. If necessary,

uncontaminated air should be obtained from remote or outside

sources.