beautypg.com

A.O. Smith HW 610 User Manual

Page 19

background image

19

NO.

SUGGESTED ITEMS FOR INSTALLATION

1

Short pipe nipple and pair of boiler loop tees in piping

between system supply and return. One set per each group

of boilers.

2 Boiler pipe loop. See piping sizing data.

3 Boiler circulator. See pump sizing data.

4 Thermometer.

5 Theraltimeter.

6 Plug cock to control flow rate.
7 Safety flow switches. For interlock with other systems or

instead of low water cutoff.

8 Relief valve.

9

With one -300, -399 or -420 item 9 is - sensing element of

remote control.

With a group of -300's, -399's or -420's, item 9 is - for 1st

boiler, the sensing element as above. For additional boilers,

install a 2nd limit control if required by local codes. With

any -520, -610 or 670 boilers, install 2nd limit control here if

required by local code.

BOILER INLET - OUTLET SIZES

10 HW-300 - 1-1/4", HW-399 - 1-1/2", HW-420 - 1-1/2",

HW-520 & HW-610 - 2".

10 HW-300 - 1-1/4", HW-399 - 1-1/2", HW-420 - 1-1/2", HW-520

& HW-670 - 2".

MINIMUM BRANCH SIZES TO BOILERS

11

HW-300 - 1-1/4" HW-520, 610 (Single boiler

HW-399 - 1-1/2" per pump) 2"

HW-420 - 1-1/2"

11

HW-300 - 1-1/4" HW-520, 670 (Single boiler

HW-399 - 1-1/2" per pump) 2"

HW-420 - 1-1/2"

12

Flow control valve. Required only if flow rate of system

primary is excessive for size of boiler branch tees or if chilled

water main is above boilers.

13 System supply temperature thermometer.
14 Boiler headers for three (3) boilers can be larger than pipe

loop, if desired, to aid in balancing.

The system flow rate is selected to give the desired system

temperature drop - depending on the design criteria.

The boiler generator flow rates, on the other hand, should be

selected to give the temperature rise through the generator that is

both economical and offers the best generator efficiency.

The boiler temperature rise is normally between 10

0

C and 20

0

C (20

0

F

and 40

0

F). The system temperature that will be introduced to the

boiler (inlet temperature) plus the selected boiler temperature rise

selected from PUMP AND PIPE SIZING DATA should not exceed

the high limit control setting of 115

0

C (240

0

F).

There should be a relation of the minimum system load to the size

boiler selected as the first firing or base boiler. This will stabilize

operation during minimum load periods.

B. Commercial Boiler Replacements

Application of LINEAR-TEMP

®

to a commercial boiler replacement

with an old multiple pump installation is an excellent way to modernize

the system. The A. O. Smith boiler(s) should be installed on a pipe

loop with a separate circulating pump selected from PUMP AND

PIPE SIZING DATA TABLE.

Figure 12 shows a line drawing of how the system headers should be

connected to the pipe loop installed with the replacement boiler(s).

Make-up water connections and accessories are not shown.

SCHEMATIC OF THE LINEAR-TEMP

®

SYSTEM

FIGURE 12.

Supply and return headers of the old system should be connected

to the boiler loop with a pair of tees set close together. The boiler

loop pump and the boiler(s) should be wired to operate only when

any of the system pumps are in operation. The number of zone

pumps that may be in operation at any particular time will take

their required flow rate out from the first tee in the boiler piping.

This water will be circulated through the proper branches from

the supply header to the zones calling for heat. The water will be

brought back to the return header and then into the second tee in

the boiler pipe loop. There will be no conflict between the boiler

pump and the zone pumps when the two tees in the boiler loop

are placed close together.
Normal use of flow control valves is required to prevent cross

circulation of zones as with any multiple pump system. Flow control

is not required on boiler circuit.
Attention should be given to balancing gas inputs and water flow

rates. Large systems with multiple boilers should include main water

temperature control (with or without outdoor reset) to stage the boilers

on and off in relation to the load on the system.

3. WATER SUPPLY LINE
These boilers can be used ONLY in a forced circulation hot water

heating system. Since most forced circulation systems will be of

the closed type, install the water supply line as shown on piping

diagrams, Figure 7 to 11 on pages 14 and 18.
Fast filling of large pipe, old radiator installations and pressure

purging of series loop systems (where high pressures are not

available) requires bypassing of the pressure reducing valve.

Generally, pressure purging is not possible with a well pump system.

High point air venting is essential.
If the system is of the open type, a pressure reducing valve

will not be required as the water supply to the system will be

controlled by a manually operated valve. An overhead surge

tank is required.

4. EXPANSION TANK

CAUTION

A closed system will exist if a check valve (without bypass), pressure

reducing valve (without bypass), or a water meter (without bypass) is

installed in the cold water line between the water heater and street

main (or well).
Excessive pressure may develop causing premature tank failure or

intermittent relief valve operation. This is not a warranty failure. An

expansion tank or a similar device may be required in the inlet supply

line between the appliance and the meter or valve to compensate for

the thermal expansion of water under supply pressure, see Figure 7

on page 14.
An air separator as shown in the piping diagrams is recommended

especially for modern commercial hydronic systems.