Venting – A.O. Smith HW 610 User Manual

Page 14

background image

14

INSTALLATION CLEARANCES

These boilers are approved for installation on combustible flooring

in an alcove with minimum clearance to combustibles of:

TABLE 4

HW

300

HW

399

HW

420

HW

520

HW

610 & 670

TOP

28" (711.2) 32" (812.8) 24" (609.6) 24" (609.6) 24" (609.6)

SIDES

6" (152.4) 6" (152.4) 24" (609.6) 24" (609.6) 24" (609.6)

REAR

6" (152.4) 6" (152.4) 24" (609.6) 24" (609.6) 24" (609.6)

VENT

6" (152.4) 6" (152.4) 6" (152.4) 6" (152.4) 6" (152.4)

Two inch (50.8mm) clearance is allowable from combustible

construction for hot water pipes.

Sufficient area should be provided at the front and rear of the unit

for proper servicing. Clearances of 24 inches (609.4mm) in the

rear and 48 inches (1,219mm) in the front are required by code.

In a utility room installation, the door shall be wide enough to allow

the boiler to enter or to permit the replacement of another appliance

such as a water heater.

LEVELING

Each unit should be checked after installation to be certain that it is level.

If the unit is not level, insert metal shims under the legs of the unit

to correct this condition.

SYSTEM CONNECTIONS

The system installation must conform to these instructions

and to the requirements of the local code authority having

jurisdiction. Good practice requires that all heavy piping be

supported.

VENTING

A TYPICAL BOILER INSTALLATION

FIGURE 7.

VENTING THE BOILER - STANDARD VENTING

WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING

THE BOILER MUST BE FOLLOWED TO AVOID CHOKED

COMBUSTION OR RECIRCULATION OF FLUE GASES.

SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE

AND ASPHYXIATION.

TYPE B VENTING MAY BE USED WITH THESE BOILERS. ALL

LOCAL UTILITY REGULATIONS ON VENTING SHOULD BE

FOLLOWED.

For boilers for connection to gas vents or chimneys, vent sizing,

installation and termination shall be in accordance with the

current edition of the National Fuel Gas Code, ANSI Z223.1, or

CAN/CSA B149.1, Installation Codes, or applicable provisions

of the local building codes.

Vent connectors serving appliances vented by natural draft shall

not be connected into any portion of mechanical draft systems

operating under positive pressure.

The minimum distance from adjacent public walkways, adjacent

buildings, openable windows and building openings shall not be

less than those values specified in the National Fuel Gas Code,

ANSI Z223.1 and/or CAN/CSA B149.1, Installation Codes;

Stack or chimney must be a minimum height of 12" (305mm)

above the annual snow fall to prevent blockage.