beautypg.com

A.O. Smith HW 610 User Manual

Page 15

background image

15

Building materials must not come in contact with combustion

products from stack or chimney, due to the degradating properties

of flue products.

Flue products must have a minimum clearance of 4 feet (1.22m)

horizontally from, and in no case above or below, unless a 4-foot

(1.22m) horizontal distance is maintained, from electric meters, gas

meters, regulators and relief equipment.

CAN/CSA B149.1, Installation Code specifies a 6 foot horizontal

vent terminal clearance to gas and electric meters and relief devices

(this clearance is specified as 4 feet in the U.S. under the National

Fuel Gas Code, ANSI/Z223.1). Therefore instruction, which specifies

compliance with the 4 foot clearance, as applies in the U.S. only, and the

CAN/CSA B149.1 Installation Code applies in Canada.

1. DRAFT HOOD
The draft hood furnished with this boiler must be installed without

alteration. Provision must be made if the boiler is installed in confined

space or a small boiler room to accommodate draft hood spillage and

avoid risks described above. The upper air opening called for in the

AIR REQUIREMENTS section of this manual is for this purpose.

2. VENT CONNECTION
Size and install proper size vent pipe. Do not reduce pipe size to

less than that of the draft hood outlet.

Horizontal runs of vent pipe shall be securely supported by

adequately placed (approximately every 4 feet or 1 meter), non-

combustible hangers and/or slip joints suitable for the weight

and design of the materials employed to prevent sagging and

to maintain a minimum upward slope of 1/4" (21mm/m) per foot

from the boiler to the vent terminals, see Figure 8. Dampers or

other obstructions must not be installed in the vent. Be sure

that the vent pipe does not extend beyond the inside wall of

the chimney.

VENT PIPE INSTALLATION

FIGURE 8.

Where a continuous or intermittent back draft is found to exist the

cause must be determined and corrected. A special vent cap may

be required. If the back draft cannot be corrected by the normal

methods or if a suitable draft cannot be obtained, a blower type

flue gas exhauster may be employed to ensure proper venting and

correct combustion if permitted by local codes.

WARNING

FAILURE TO CORRECT BACK DRAFTS WILL CAUSE AIR

CONTAMINATION AND UNSAFE CONDITIONS.

Vent connectors serving appliances vented by natural draft shall not

be connected into any portion of mechanical draft systems operating

under positive pressure.

3. CONNECTING BOILER TO A COMMON VENT

Do not connect the boiler to a common vent or chimney with solid

fuel burning equipment. This practice is prohibited by many local

building codes as is the practice of venting gas fired equipment to

the duct work of ventilation systems.

Where a separate vent connection is not available and the vent pipe

from the boiler must be connected to a common vent with oil burning

equipment, the vent pipe should enter the common vent or chimney

at a point ABOVE the flue pipe from the oil fired unit.

Where two or more appliances vent into a common vent connector

or manifold, the area of the common vent or vent connector should

at least equal the area of the largest vent connector plus 50% of the

areas of the additional draft hood outlets.

When removing a boiler from a system with a common vent, use

the following steps:

Be sure the other appliances connected to the common vent are

not in operation.

Seal any unused openings in the common venting system.

Visually inspect the venting system for proper size and horizontal pitch

and determine there is no blockage or restriction, leakage, corrosion

and other deficiencies which could cause an unsafe condition.

WARNING

Ensure sufficient supply and ventilation air. Under no circumstances

should the equipment room where the boiler is installed ever be under

negative pressure. Insufficient air supply can interfere with combustion

and ventilation of this boiler resulting in unsafe conditions.

Insofar as is practical, close all building doors and windows and

all doors between the space in which the appliances remaining

connected to the common venting system are located and other

spaces of the building. Turn on clothes dryers and any appliance not

connected to the common venting system. Turn on any exhaust fans,

such as range hoods and bathroom exhausts, so they will operate

at maximum speed. Close fireplace dampers.

Place in operation the appliance being inspected. Follow the

lighting instructions. Adjust thermostat so appliance will operate

continuously.

Test for spillage at the draft hood relief opening after five minutes of

main burner operation. Use the flame of a match or candle.

After it has been determined that each appliance remaining connected

to the common venting system properly vents when tested as outlined

above, return doors, windows, exhaust fans, fireplace dampers and

any other gas burning appliance to their previous conditions of use.

Any improper operation of the common venting system should be

corrected so the installation conforms with the current edition of

CAN/CSA B149.1 (current edition). When resizing any portion of

the common venting system, the common venting system should

be resized to approach the minimum size as determined using the

appropriate tables in CAN/CSA B149.1.