FIGURE 31.

TWO HW-300's, HW-399's, HW-420's, HW-520's, HW-610's OR HW-670's UP-FLOW MODEL

COMMERCIAL BOILER WITH HORIZONTAL TANK

IMPORTANT

THE INSTALLATION OF SAFETY FLOW SWITCH AS SHOWN

IS REQUIRED TO PROTECT THE BOILER IN CASE OF WATER

SERVICE INTERRUPTION OR CIRCULATOR FAILURE.

+ PIPING AND FITTINGS BETWEEN GATE VALVES AND

BOILERS SHOULD BE BRASS OR BRONZE. OTHER

PIPING SHOULD CONFORM TO LOCAL CODES.

GATE VALVES ARE SHOWN FOR SERVICING BOILER.
HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.

* PRESSURE RELIEF VALVE RATING SHOULD NOT

EXCEED PRESSURE CAPACITY OF ANY COMPONENT

IN THE SYSTEM.

** INSTALL THERMOMETER AND PRESSURE RELIEF IN

OPENINGS PROVIDED ON HW-520, HW-610 & HW-670.

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT

FIXTURES. SEE TANK TEMPERATURE CONTROL WARNING ON PAGE 11. IF HIGHER

PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER

OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.

WIRING - FIGURES 21 to 27 on

pages 28 to 32.

INSTALL IN ACCORDANCE

WITH ALL LOCAL CODES

USE THIS TABLE FOR CORRECT

PUMP AND WATER PIPE SIZE

Model

Number

Minimum

Pipe Size

(Inches)

B & G

Pump

Size

*Armstrong

Pump Size

A

B

HW-300

2"

1-1/2"

2"

S-35

HW-399

2"

1-1/2"

2"

S-35

HW-420

2"

1-1/2"

2"

S-35

HW-520

2"

1-1/2"

2"

S-35

HW-610/670

2-1/2"

1-1/2"

2-1/2"

S-45 2-1/2"

* Assumes 50 equivalent feet of piping or less.