Troubleshooting – A.O. Smith HW 610 User Manual

Page 47

background image

47

TROUBLESHOOTING

CER-TEMP 80 RECOVERY SYSTEM CHECKOUT PROCEDURE

Use this checkout for Cer-Temp 80 Recovery Systems. (For hot water supply application only)

Checkout Sequence

System Operation

Cause

Remedy

Contact

Incorrect

Set tank temperature

control (thermostat) 20°F

(10°C) below tank water

temperature.

Circulating pump and

burner shut off.

With thermal balancer,

pump off delay of

approximately 2 minutes.

Pump and burner remain

on.

Tank temperature control

(thermostat) defective.

Replace.

System wiring is

incorrect.

Correct wiring.

Circulating pump on.

Pump wired for

continuous operation.

Correct wiring.

Burner on.

Gas valve stuck or

defective.

Correct or replace

valve.

System wiring is

incorrect.

Correct wiring.

Set tank temperature

control (thermostat) 20°F

(10°C) above tank water

temperature.

Circulating pump and

burner on.

Circulating pump on.

High limit control set too

low.

Replace. (If problem

proven to be at this

control by applying

jumper to terminals.)

High limit control

differential too wide.
System wiring is

incorrect.

Correct wiring.

Coil protector switch has

activated.

Remove control cover,

depress reset button.

Gas valve or wiring

defective.

Check wiring. Repair or

replace valve.

Circulating pump and

burner off.

Power off or system

wiring is incorrect.

Check power supply

and wiring.

Tank temperature control

(thermostat) defective.

Replace.

Burner on.

System wiring is

incorrect.

Correct wiring.

Boiler outlet temperature

exceeds 210°F (100°C). Circulating pump on.

Circulating pump and

burner on.

High limit control

defective, or set too high

(max. should be set at

200°F).

Replace.

Set tank temperature

control (thermostat)

for desired water

temperature.

System maintains desired

water temperature.